Rockwell Automation 284G ArmorStart - Safety Version - Getting Started User Manual

Page 15

Advertising
background image

Publication 284GS-QS001A-EN-P - May 2009

15

Setting the Motor OL Current

The product should now be configured and communicating on the network.
The last step is to program the proper motor OL current setting
(Parameter 133). This can be accomplished by using software such as
RSNetWorx for DeviceNet or a handheld DeviceNet tool.

Use the software to access the device parameters screen. By default the
motor OL current is set to the minimum motor OL current setting for the
device. Set this parameter to the desired value and download to the device.

Select Motor OL Current (Parameter 133) and enter a value that
corresponds to the FLA of the motor connected to the ArmorStart. Make
sure the Single radio button is selected and then select Download to Device.

The proper motor protection is now in place.

Figure 9 RSNetWorx Parameter Screen

Advertising