Operation 15 – Rockwell Automation 836E Solid-State Pressure Sensors User Manual

Page 15

Advertising
background image

Operation

15

4.1.4

Output Setting

•

Hysteresis mode
The hysteresis mode allows for two-point control. Depending on the pressure p, the
hysteresis can be set via the set point SP and the reset point RSP.

•

Window mode
The window mode enables process pressure range monitoring.

•

Analog output mode
The analog output mode returns a 4…20 mA signal proportional to the measured value.
The upper and lower range values can be set by the user.

•

Factory default settings
Set point SP 1: 45%; Reset point RSP 1: 44.5%
Set point SP 2: 55%; Reset point RSP 2: 54.5%
Analog output: Lower Range Value (LRV) 0%; Upper Range Value (URV) 100%

•

Each set point can be selected as Normally Open (N.O.) or Normally Closed (N.C.)

•P01-PTx3xxxx-05-xx-xx-xx-001

Fig. 7: ➀ Hysteresis mode, ➁ Window mode, ➂ Switch status of NO contact, ➃ Switch status of NC

   contact

Note: SP = set point; RSP = reset point