Installation Instructions

Installation must be in accordance with the following steps and stated specifications and should be
carried out by suitable competent personnel.
Adherence to the recommended maintenance instructions forms part of the warranty.

This switch has an integrated latch and guard stop for use on lightweight guard doors.

This device is intended to be part of the safety related control system of a machine. Before installation,
a risk assessment should be performed to determine whether the specifications of this device are suit-
able for all foreseeable operational and environmental characteristics of the machine to which it is to
be fitted. Refer to Technical Specifications for Certification information and ratings.

ATTENTION:

The presence of spare actuators compromise the integrity of the safety sys-
tems. Personal injury or death, property damage or economic loss can result.
Appropriate management controls, working procedures and alternative protec-
tive measures should be introduced to control their use and availability.

Technical Specification

Safety Ratings
Standards

IEC60947-5-3, IEC61508, ISO 13849-1

Safety Classification

Cat. 4 Per ISO 13849-1, SIL CL3
PFH

D

: 1.12 x 10

-9

Dual channel interlock may be suitable for

Functional Safety Data

use in application up to PLe (according to
ISO 13849-1) and for use up to SIL3
systems (according to IEC 62061) depending
application characteristics.

Certifications

CE marked for all applicable directives, cULus
(UL 508), and TÜV.

Operating Characteristics

Sensing Distance, Assured ON

4 mm

Sensing Distance, Assured OFF

25 mm

Maximum output current (all outputs)

200 mA

Input Current

50 mA (no load supply current)

Operational Current, Min.

³ 1 mA DC

Off-state Current

< 0.5 mA DC

Maximum # of switches, connected in series

Unlimited. See unit response time section

Operating Voltage

24V DC +10% / -15% Class 2 SELV power supply

Utilization category according to IEC 60947-5-2 DC-12 & DC-13
Ue

24V

Ie

200mA

Frequency of operating cycle

0.25 Hz

Response Time (Off)

60 ms

Case Material

Grilamid

Actuator Material

Grilamid / PBT

Outputs (Guard door closed, Actuator in place)

Outputs

Description

Status

Safety

2 x PNP, 0.2 A max.

ON (+24vdc)

Auxiliary

1 x PNP, 0.2 A max.

OFF (0vdc)

Environmental

Operating Temperature

-10…+55°C (+14…+131°F)

Operating Humidity

5% -95% relative

Washdown rating

NEMA 3, 4X, 12,13, IP66, IP67, IP69K

Shock & Vibration

IEC 60068-2-27

30 g, 11 ms

IEC 60068-2-6

10…55Hz

Radio Frequency

IEC 61000-4-3
IEC 61000-4-6

SensaGuard

TM

Installation Instructions 3