Diagnostic, Typical wiring diagram, 8sensaguard – Rockwell Automation 440N SensaGuard Integrated Latch Unique Coded Installation Instructions User Manual
Page 8: Installation instructions

8
SensaGuard
TM
Installation Instructions
Note: Refer to Technical Specifications for Certification information and ratings.
Note: Refer to Technical Specifications for Certification information and ratings.
Diagnostic
Unit Indicators (per IEC 60073)
State
Status
Troubleshooting
Off
Not Powered
NA
Status/Diag
Red
Not Safe, OSSD not active
NA
LED
Green
Safe, OSSD active
NA
Green flash
Power up test or OSSD
Check 24V DC or OSSD inputs
inputs not valid
(yellow and red wire)
Red Flash
1 Hz Flash OSSD Fault
OSSD fault —check OSSD
4 Hz Flash Recoverable /
outputs are not shorted to GND,
Non-recoverable Fault
24V DC or each other. Cycle power.
Typical Wiring Diagram
Description
Plastic
8-Pin Micro (M12)
Grey
Safety A
Red
Safety A+
Pink
Safety B
8-Pin Cordset
Yellow
Safety B+
889D-F8AB-*
White
Aux A
or cable version
Brown
24V DC+
Blue
0V
Green
N/A
* Replace symbol with 2 (2m), 5 (5m) or 10 (10m) for standard cable lengths.
2-24V DC+
1-Aux A
7-0V
6-Safety B
3-N/A
8-Safety A+
4-Safety B+
5-Safety A