ArmorConnect Cable Ratings
The ArmorConnect Power Media cables are rated per UL Type TC 
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or 
STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional 
information regarding ArmorConnect Power Media see the ArmorStart 
User Manual.
Branch Circuit Protection Requirements for ArmorConnect™ 
Three-Phase Power Media 
When using ArmorConnect Three-Phase Power Media, only fuses can be 
used for the motor branch circuit protective device, for the group motor 
installations. The recommended fuse types are the following: Class CC, T, 
or J type fuses. For additional information, see the ArmorStart User 
Manual.
Terminal Designations
Description
Color Code
A1 (+)
Control Power Input
Blue
A2 (-)
Control Power Common
Black
PE
Ground
Green/Yellow
1/L1
Line Power - Phase A
Black
2/L2
Line Power - Phase B
White
3/L3
Line Power - Phase C
Red