Rockwell Automation 284A ArmorStart with ArmorPoint Backplane - Getting Started User Manual
Page 22
 
22
Publication 284A-QS001C-EN-P - July 2006
Figure 17 Array Size Parameter
Armor_Start_System.Num_Devices defaults to zero and is defined as the 
total number of ArmorStart products connected to the control system that 
need to be configured. It is important that this value be set before the 
configuration routine is executed.
It is to the users best advantage to trim the structures down to the minimum 
values that match their system because this will save a considerable amount 
of Logix processor memory. However, some room should be left in the 
structures to handle any future additions of ArmorStart devices to the 
system.
Adding Devices to the Configuration Structure
Once the three major System level parameters are entered, it is up to the 
user to enter in, each of the ArmorStart devices configuration information. 
These parameters are defined by the slot in the Logix chassis where the 
EtherNetIP or ControlNet communication card resides. The next parameter 
is the EtherNetIP IP or ControlNet node address of the 1738 communication 
adapter containing the ArmorStart. Lastly, the slot number on the 
ArmorPoint subnet where the ArmorStart is connected also needs to be 
entered. An optional parameter is a string that can be entered with a 
description of the function of the ArmorStart device. Each device will be 
configured by entering its data into a different block of the 
Armor_Start_System.Device[] array.
The Following shows the configuration for a communication card in the 
Logix chassis 2, AENT IP address 192.168.1.10 and Point I/O slot 3. The 
logic determines whether the network is EtherNetIP or ControlNet 
depending on whether the ENET_IP_Addr field is blank or the 
CNET_Address is zero. One of these two fields must be filled out for the 
logic to work correctly. The Armor_Descriptor field is optional and is used 
to more easily identify the ArmorStart as to its function in the system.