Rockwell Automation 284A ArmorStart with ArmorPoint Backplane - Getting Started User Manual
Page 20
 
20
Publication 284A-QS001C-EN-P - July 2006
I/O Tree Overview
In order to transfer I/O information, the ArmorStart needs to be added to the 
I/O tree of the Logix processor. The details of doing this are outside of the 
scope of these instructions, but screen captures of the completed 
configuration are included below for reference. The configuration below 
shows the EtherNetIP card in the Logix chassis slot 1. The 1738-AENT 
module is always located at slot zero in the subnet and the ArmorStart 
device is located in slot 2 on the subnet. These slots are circled below for 
you reference.
Figure 13 Logix Processor I/O Tree
The only configuration that the user needs to be concerned with for the 
ArmorPoint communication adapter is either the EtherNet IP address or the 
ControlNet node address.
Since there currently is no profile for an ArmorStart device in the I\O Tree, 
the 1738-MODULE profile needs to be used as a generic profile. The 
standard configuration for an ArmorStart 284A, using this profile is shown 
below.
Figure 14 ArmorStart Configuration using 1738-MODULE Profile