Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual
Page 38

38
Rockwell Automation Publication 1412-UM001D-EN-P - September 2012
Chapter 3
Display Modes
This table lists the capture threshold levels, based on the probe in use (for the
current channels) and voltage at the different percent selections.
Transients are detected by comparing all 256 samples on the current cycle with
their counterparts from the previous cycle for each active input channel. Should
any one sample deviate from its counterpart by the selected percentage value in
the set up, this will be considered a transient and the data will be captured.
When capture occurs, four cycles are recorded for each input. These include the
trigger cycle, the previous cycle to the trigger and the two cycles that follow the
triggered cycle. All active inputs will be captured.
Thresholds
100%
50%
20%
10%
5%
2%
1%
MN93
200 A
100 A
40 A
20 A
10 A
4 A
2 A
MN193 (100A)
100 A
50 A
20 A
10 A
5 A
2 A
1 A
MN193 (5A)
[(primary x 5) ÷ (secondary)] x (percent x 100)
SR193
1000 A
500 A
200 A
100 A
50 A
20 A
10 A
AMPFLEX 193
2900 A
1400 A
580 A
290 A
140 A
58 A
29 A
MR193
1000 A
500 A
200 A
100 A
50 A
20 A
10 A
2999A Ratio
Adapter
3000 A
1500 A
600 A
300 A
150 A
60 A
30 A
1A Ratio Adapter
1 A
0.5 A
0.2 A
0.1 A
0.05 A
0.02 A
0.01 A
Voltage
480V
240V
96V
48V
24V
9.6V
4.8V