Opening previously stored transients, Storing the trigger – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

39

Display Modes

Chapter 3

Opening Previously Stored Transients

The screen below can be accessed with the retrieve button

. It displays a list

transients previously stored in the memory.



The status bar at the top displays the memory filled by stored transients.



Name and transient number (from 01…50) for each stored transient.



Transient recording time and date are displayed for each transient.

To select a transient, press the Up/Down Cursor buttons, then press

Enter.

To delete a selected transient, press the Trash Can button , then press

Enter.

Storing the Trigger

The threshold T in percent, defined as an envelope width (over and under) the

last cycle of signal V or A input signal. Its width W is calculated with the nominal

measurement range R for a channel (depending on the selected current sensor).

W = T x R

EXAMPLE

Using the SR193 probe and a 2% trigger level, the width would

be 1000A x 2% = 20 A. Therefore, a deviation of ±20 A will

cause a transient event to be captured.

07/25/02 10:56

100%

SELECTION OF TRANSIENT

TEST 05

TEST 04

TEST 03

TEST 02

TEST 01

05/07/02 14:31:41

05/07/02 14:31:41

05/07/02 14:31:21

05/07/02 14:31:04

05/07/02 14:31:04

1

2

3