Onfigurable, Tems – Rockwell Automation 1609-P3000N_H_A_E 3000 / 5000 VA Uninterruptible Power Supply User Manual

Page 10

Advertising
background image

9

U

SER

C

ONFIGURABLE

I

TEMS

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

N

ETWORK

M

ANAGEMENT CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELEC TABLE

C

HOICES

D

ESCRIPTION

Automatic Self-Test

Every 14 days
(336 hours)

Every 7 days(168 hours),
14 days (336 hours)
On Startup Only,
No Self-Test

Set the interval at which the
UPS will execute a self-test.

UPS ID

UPS_IDEN

Up t o eight characters to
define the UPS

Uniquely identify the UPS, (i.e.
server name or location) for
network management purposes.

Date of Last Battery
Replacement

Manufacture Date

Date of
Battery Replacement
mm/dd/yy

Reset this date when you replace
the battery modules.

Minimum Capacity
Before Return from
Shutdown

0 percent

0, 15, 25, 35, 50, 60, 75,
90 percent

Following a low-battery
shutdown, the battery modules
will be charged to the specified
percentage before powering
connected equipment.

Alarm Delay After
Line Failure

5 second delay

5 or 30 second delay
At Low Battery
Never

Mute ongoing alarms or disable
all alarms permanently.

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,
720, 960 seconds

Set the interval between the time
when the UPS receives a
shutdown command and the
actual shutdown.

Duration of
Low Battery Warning.

2 minutes

PowerChute
software provides
automatic,
unattended
shutdown when
approximately 2
minutes of battery
operated runtime
remains.

2, 5, 7, 10, 12, 15, 18,
20 minutes

The low battery warning beeps
are continuous when two
minutes of run time remain.

Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.

Synchronized Turn-on
Delay

0 seconds

0, 20, 60, 120, 240, 480,
720, 960 seconds

The UPS will wait the specified
time after the return of utility
power before turn-on (to avoid
branch circuit overload).

High Bypass Point

+10% of
output voltage
setting

+5%, +10%, +15%,
+20%

Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.