Use one of the following cable types to connect the UPS to the EPO switch:

CL2: Class 2 cable for general use

CL2P: Plenum cable for use in ducts, plenums, and other sp aces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor to floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).

Terminal Mode to Configure UPS Parameters

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.

Connect the serial cable to the serial com connector on the back of the UPS.

1609-P5000E models only: Remove the 1609-NMC network management card from the slot located
in the rear of the unit.

1. EXIT the PowerChute Business Edition using the following steps:

From the Desktop, go to Start => Settings => Control Panel => Administrative Tools =>
Services.

Select APC PCBE Server and APC PCBE Agent – right click the mouse and select Stop.

2. Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.

3. Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

ü

bits per second - 2400

ü

data - bits 8

ü

parity - none

ü

stop bit - 1

ü

flow control - none

Press ENTER

4. Example for setting the number of external battery packs:

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Follow the prompts:

Press 1 to modify UPS Settings. Press e (or E) to modify the number of battery
packs. Enter the number of battery packs, including the internal battery pack
(Number of packs: 1= internal battery module,
2 = 1 external battery pack, 3 = 2 external battery packs, etc.).
Press ENTER.

Follow the prompts.

5. Exit the terminal program.

6. 1609-P5000E models only: Re-install the 1609-NMC network management card in the slot

located in the rear of the unit.