Wiring and Connecting the UPS
C
ONNECTING
UPS
USING POWER CORD
:
3000
VA
U
NITS
1609-P3000N – Use captive 8 ft cord. NEMA L5-30 Plug is attached to this cord.
1609-P3000H – Use in captive 8 ft cord. NEMA L6-30 Plug is attached to this cord.
1609-P3000A – User must supply p ower cord. Power cord must mate with IEC 320 C20 inlet.
H
ARDWIRING
I
NSTRUCTIONS
:
1609-P5000E
•
Wiring must be performed by a qualified electrician.
•
Install a high magnetic 30/32 A utility circuit breaker,
(Allen-Bradley Catalog Number 1489-A2C300).
•
Adhere to all national and local electrical codes.
•
Use #10 AWG gauge (5 sq. mm) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5 sq. mm) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral).
Use an appropriate s train relief (not included).
5. Switch the utility circuit breaker ON.
6. Check line voltages.
7. Replace the access panel.