2-6
Installation Standard Enclosure
1512A-UM102B-EN-P – June 2013
0.219 Pilot Holes (QTY. 3)
0.281 Clearance Holes (QTY. 5)
0.219 Pilot Holes (QTY. 5)
0.281 Clearance Holes (QTY. 3)
Side Bus Access Cover
Front
(All dimensions in inches)
Front
Figure 2.4 – Joining Sections
A T T E N T I O N
A T T E N T I O N
This procedure requires contact with medium
voltage components. To avoid shock hazards, lock
out incoming power before working on the
equipment. (See Power Lockout Procedure, page
5-3). Verify with a hot stick or appropriate
voltage measuring device that all circuits are
voltage free. Failure to do so may result in severe
burns, injury or death.
Rear Access
1) Remove the hardware securing the center rear bus access cover
(Figure 2.5).
2) Remove the center rear bus access cover.
3) Once the rear bus cover is removed you will see the three power bus
bars and grounding bus (Figure 2.6).
Access to the Power Bus