Removing the contactor – Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual
Page 57

Maintenance 5-9
1512A-UM102B-EN-P – June 2013
Removing the Contactor
To avoid shock hazards, lock out incoming power
(see page 5-3) before working on the equipment.
Verify with a hot stick or appropriate voltage
measuring device that all circuits are voltage free.
Failure to do so may result in severe burns, injury
or death.
1) Complete the Power Lockout Procedure (see page 5-3).
2) Disconnect the control wiring harness from the wire plug at the
lower left side of the contactor (See Figure 5.6)
3) Use a 9/16 in. socket wrench to disconnect the power cables from
the rear of the contactor.
4) Remove the nylon contactor bushing retaining screw from the con-
tactor interlock lever.
5) Slide the contactor interlock rod and the nylon contactor bushing
out of the groove in the contactor interlock lever (see Figure 5.7).
A T T E N T I O N
A T T E N T I O N
Figure 5.7 - Removing the Contactor (Front View)