3-8
Installation – Arc Resistant (ArcShield)
1512A-UM102B-EN-P –June 2013
A T T E N T I O N
A T T E N T I O N
This procedure requires contact with medium
voltage components. To avoid shock hazards, lock
out incoming power before working on the
equipment. (See Power Lockout Procedure, page
5-3). Verify with a hot stick or appropriate
voltage measuring device that all circuits are
voltage free. Failure to do so may result in severe
burns, injury or death.
Rear Access
1) Remove the hardware securing the center rear bus access cover
(Figure 3.6).
A T T E N T I O N
A T T E N T I O N
The rear cover plates are made from 12 gauge
metal and are mounted in board of the main
structure. The cover will drop inside if care is not
taken as you remove the mounting bolts.
2) Remove the center rear bus access cover.
3) Once the rear bus cover is removed you will see the three power bus
bars (Figure 3.8) and grounding bus.
Center Rear Bus
Access Cover
Side Bus
Access Cover
(A Shi ld)
Figure 3.6 – Access to Power Bus from Side and Rear of Cabinet, Typical
Access to the Power Bus