Chapter 2

Run Up/Coast Down Extension Module

See

Display the Nyquist Plot on page 27

.

Table 5 - Nyquist Plot Parameters

Parameter Name

Description

Values/Comments

Start Spd (RPM)

Sets the start speed of the recorded data for the plot.

This defaults to the Start Spd value set in the RUCD Setup screen.

See

Run Up/Coast Down Setup Parameters on page 18

.

10…3600 rpm

Stop Spd (RPM)

Sets the stop speed of the recorded data for the plot.

This defaults to the Stop Spd value set in the RUCD Setup screen.

See

Run Up/Coast Down Setup Parameters on page 18

.

10…3600 rpm

Spacing

Controls the spacing between collected spectra:

Δ

rpm is a fixed speed change between spectra.

%

Δ

rpm is a percentage speed change between spectra.

Δ

Time is a fixed time interval between spectra.

Δ

rpm +

Δ

Time is a combination of speed and time interval

settings. If speed stops changing then spectra are calculated using
the Time Interval value.

%

Δ

rpm +

Δ

Time is a combination of speed and time interval

settings. If speed stops changing then spectra are calculated using
the Time Interval value.

Δ

rpm

%

Δ

rpm

Δ

Time

Δ

rpm +

Δ

Time

%

Δ

rpm +

Δ

Time

Your selection affects the Speed Interval
and Time Interval settings.

Speed Interval (RPM)

Sets the speed interval used in calculating FFT spectra.

This parameter not used when Spacing is set to

Δ

Time.

1… 240 rpm or % rpm

Time Interval (sec)

Sets the time interval used in calculating FFT spectra.

This parameter is not used when Spacing is set to

Δ

RPM and %

Δ

RPM.

.001…604800 s

Display Units

Sets the Y-axis units.

The available units depends on the transducer used to collect data.

See

Run Up/Coast Down Setup Parameters on page 18

.

LF Cutoff

Determines whether to apply a low frequency filter (0.3 times the running
speed) to the data.

Off

On

Detection

Sets the signal detection and scaling display for the plot:

Peak - Measured RMS value multiplied by the square root of two

(1.4142).

Pk-Pk - Measured RMS value multiplied by two times the square root

of two (2.8284).

RMS - Root mean squared signal level of the input signal.

RMS

Peak

PkPk

Num Traces

Sets the number of traces or order tracks to be displayed on the plot.

Your selection determines the available number of Trace Order
parameters.

1

2

3

4

Trace Order #1-#4

The order numbers to be tracked and displayed on the plot.

This value cannot exceed the Max No Orders value set in the RUCD Setup
screen.

See

Run Up/Coast Down Setup Parameters on page 18

.

.001…166 orders