Appendix

A

1500-IN052C-EN-P – January 2007

Door Interlock Circumvention

The door interlock mechanism is designed to prevent access to the

medium voltage cell while the unit is energized. When the unit

is in operation, do not circumvent this inter-locking safety feature.

Always disconnect and lock out incoming power (see Power

Lockout Procedure, page 2) before proceeding with any adjust-

ments requiring the handle to be moved to the ON (closed) position.

Failure to do so may result in electric shock causing severe

burns, injury or death.

This Appendix provides information on how to move the isolation switch handle

from the OFF position to the ON position while the medium voltage door is open.

The interlocking safeguards in the mechanism are designed to prevent the handle

from moving to the ON position while the cabinet door is open.

• To circumvent this safety feature, use a screwdriver, or other tool, to depress

the door interlock lever in a downward movement.

• Hold the lever down while moving the handle to the ON (closed) position.

Door Interlock

Lever

Figure A.1 – Door Interlock Lever

A T T E N T I O N

A T T E N T I O N