Installation
1203–5.5 September 1995
Cable Requirements
SCANport cables are available in either male–to–male or male–to–
female configuration. You can connect cables of up to 10 meters (33
feet) from the master to the SCANport device (A in the figure
below). If you use a Port Expander (as shown in the figure below),
you need to subtract the cable length from the master to the Port
Expander from the cable length used to connect the device to the
expander (B1 + C = a maximum of ten meters).
1305 Drive
An Allen-Bradley SCANport link cable is used to connect the Serial
Communications Module to the drive (as shown below).
SCANport Connection on Serial Communications Module
1305 Drive
Human Interface
Module
Port 1
A
Port 2
Optional
Male–Female
Cable
Optional
Male–Male
Cable
B1
Port Expander
B2
C
Communications
Module
Communications
Module
AB0407B
2
3
4
5
Important: The maximum cable distance between any two devices
cannot exceed 10 meters (33 feet) of cable.
For example:
A + B1 + C
≤
10 meters
A + B2 + C
≤
10 meters
B1 + B2
≤
10 meters
SCANport Link