Configuring and Interfacing

1203–5.5 September 1995

DF1 Messaging with a 1746–BAS Module Example

This example accepts a parameter number and a value from a user
terminal and writes the data out to a SCANport–compatible device.

100 REM _____________________________________________________________

101 REM __ This program inputs a parameter number and a value

102 rem __ from a user terminal and writes it out to a scanport

103 rem __ compatible device.

104 rem __ for 1746–BAS and 1203–GD2 modules

105 rem _____________________________________________________________

110 STRING 512,127

140 REM

150 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

160 REM Setup port 1 to 9600 baud, no parity, 8 bits, 1 stop bit,

170 REM software handshaking, and battery backed ram data storage.

180 REM !!!!REMEMBER TO SET TERMINAL TO MATCH!!!!

190 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

200 MODE (PRT1,9600,N,8,1,S,R)

210 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

220 REM

230 REM Setup port 2 to 300 baud, no parity, 8 bits, 1 stop bit,

240 REM software handshaking, and battery backed ram data storage.

250 REM

260 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

270 MODE (PRT2,300,N,8,1,S,R)

280 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

290 REM

300 REM Enable DF1 driver

310 REM (20 = Setup for Full Duplex, Auto–Detect Embedded Responses,

320 REM Disable Duplicate Packet Detection, BCC error checking)

330 REM (200 = Wait 1 second for polling by Master)

340 REM (2 = 2 retries)

350 REM (0= No RTS on delay)

360 REM (0 = No RTS off delay)

370 REM (8 = 1746–BAS module address)

380 REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

390 PUSH 20

400 PUSH 200

410 PUSH 2

420 PUSH 0

430 PUSH 0

440 PUSH 8

450 CALL 108

460 REM __________________ end df1 config _____________________________

461 Print: print ”A negative parameter number exits the program ”

470 INPUT ”Offset (Parameter Number)? ”,PAR_NUM

475 IF (PAR_NUM<0) THEN GOTO 530

480 INPUT ”Control (parameter value)? ”,PAR_VALUE

481 REM encode the value as an ASCII hex string in order of LOW, HIGH

490 ASC($(1),1)=PAR_VALUE–(INT(PAR_VALUE/256)*256)

500 ASC($(1),2)=INT(PAR_VALUE/256)

510 GOSUB 550 : REM fire off the write instruction

520 GOTO 460

530 CALL 113

540 END