Contactor Product Description

1-7

1502-UM050D-EN-P – June 2013

Contactor Ampere Rating

400A

Mechanical latch trip coil inrush current
• At 120 VAC ........................................................

5.1 amps

• At 230 VAC ........................................................

N/A

Coil continuous (economized) current
• At 120 VAC ........................................................

0.13 amps

• At 230 VAC ........................................................

0.11 amps

Coil pick-up voltage
• At 120 VAC

................................................

102 VAC

• At 230 VAC ........................................................

190 VAC

Coil drop-out voltage
• At 120 VAC

...............................................

75 VAC

• At 230 VAC ........................................................

140 VAC

Mechanical latch trip coil voltage
• At 120 VAC ........................................................

102 VAC

• At 230 VAC ........................................................

N/A

Maximum closing time

– (60 Hz) ..........................................................

9.6 cycles (160 msec)

– (50 Hz) ..........................................................

8 cycles (160 msec)

Maximum opening time

– normal drop-out (60 Hz) ...............................

9.6 cycles (160 msec)

– normal drop-out (50 Hz) ...............................

8 cycles (160 msec)

– fast drop-out (60 Hz) .....................................

3 cycles 50 msec)

– fast drop-out (50 Hz) .....................................

2.5 cycles (50 msec)

Mechanical latch maximum trip time

– (60 Hz) ..........................................................

3 cycles (50 msec)

– (50 Hz) ..........................................................

2.5 cycles (50 msec)

Capacitor Switching (KVAR max.)

– 2400 V ..........................................................

800

– 4160 V ..........................................................

1400

– 6900 V ..........................................................

2000

The 120 VAC control voltage is rectified for the contactor coils.

At rated control voltage