Rockwell Automation 1502 400 Amp Medium Voltage Contactor (Series D) User Manual

Page 37

Advertising
background image

Maintenance

4-9

1502-UM050D-EN-P – June 2013

Auxiliary Assembly

Retaining Bolt

Closing Coil

Hold-in Coil

Retaining Ring

Auxiliary Assembly

Auxiliary Assembly

Retaining Bolt

Closing Coil

Hold-in Coil

Retaining Ring

Auxiliary Assembly

Figure 4.11 – Coil Removal

4. Disconnect the coil leads (take note of their location). Connect the leads

of the new coil, making sure that all metal-oxide varistors (MOVs) and/or
diodes are secure. Refer to the appropriate wiring diagram in this manual
if further control wiring details are required.

5. Slide the new coil into position and install the retaining ring on the core.

Install the auxiliary assembly leaving the retaining bolt loose for adjustment
later. See the Auxiliary Contact Set-up Procedure (page 4-10) for
determining the position of the auxiliary assembly.

6. Install the armature plate, auxiliary actuator and stop bracket. Position the

stop bracket by resting it lightly against the armature plate.

Advertising