Coil replacement procedure – Rockwell Automation 1502 400 Amp Medium Voltage Contactor (Series D) User Manual

Page 36

Advertising
background image

4-8

Maintenance

1502-UM050D-EN-P – June 2013

Coil Replacement Procedure

To avoid shock hazards, lock out incoming power and
disconnect the control plug from the contactor before
working on the unit. Verify with a hot stick or meter that all
circuits are voltage free. Failure to do so may result in severe
burns, injury or death.

Refer to Chapter 6 for the part number(s) required for this procedure.

1. Remove the auxiliary actuator, front stop bracket and armature plate as

shown in Figure 4.10. Note: do not remove the bolts which secure the stop
bracket, simply loosen them and slide the bracket out (on older contactors,
the bolts must be removed from the underside of the contactor housing in
order to remove the stop bracket).

Auxiliary Actuator

Stop Bracket Bolts

Armature Stop Bracket

Armature Plate

Auxiliary Actuator

Stop Bracket Bolts

Armature Stop Bracket

Armature Plate

Figure 4.10 – Access to Coils

2. Remove the retaining ring from the core of the coil you wish to replace as

shown in Figure 4.11.

3. Loosen the auxiliary assembly retaining bolt and slide the assembly and

the coil forward and out of the contactor as shown in Figure 4.11.

A T T E N T I O N

A T T E N T I O N