Mounting the adapter and i/o modules, Mini mum spacing, Panel mounting – Rockwell Automation 1769-ADN Compact I/O DeviceNet Adapter User Manual

Page 11: Minimum spacing

Advertising
background image

Compact I/O 1769-ADN DeviceNet Adapter 11

Rockwell Automation Publication 1769-IN001C-EN-P - February 2013

Mounting the Adapter and I/O Modules

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50mm (2in) of
space on all sides for adequate ventilation, as shown:

Panel Mounting

Mount the adapter or module to a panel using two screws per adapter or module. Use M4 or #8
panhead screws. Mounting screws are required on every module. This figure illustrates panel
mounting using the dimensional template.

ATTENTION: During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the adapter or modules. Debris
that falls into the adapter or modules could cause damage on power up.

1769 I/O

1769 I/O

1769 I/O

End Cap or

Ca

bl

e

42124

1769 I/O

1769 Power

S

upply

Side

Side

Bottom

Top

1769 I/O

1769 I/O

1769-

ADN

For more than 1 module: Number of modules x 35mm (1.38in)

28.5

(1.12)

35

(1.38)

132

(5.197)

(4.826+0.008)

122.6+0.2

1769-A

D

N

1769 Power Supply

176

9 I

/O

Right End C

ap

mm (in)

Hole spacing tolerance:
+0.4mm (0.016in).

42121

(1.38)

35

70

(2.76)

(1.58)

40

35

(1.38)

176

9 I

/O

Advertising