North american hazardous location approval – Rockwell Automation 1769-ADN Compact I/O DeviceNet Adapter User Manual

Page 4

Advertising
background image

4 Compact I/O 1769-ADN DeviceNet Adapter

Rockwell Automation Publication 1769-IN001C-EN-P - February 2013

North American Hazardous Location Approval

The following information applies when operating
this equipment in hazardous locations.

Informations sur l’utilisation de cet équipement en
environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use
in Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within
a system, the most adverse temperature code (lowest "T"
number) may be used to help determine the overall
temperature code of the system. Combinations of equipment
in your system are subject to investigation by the local
Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.

WARNING:
Explosion Hazard -
• Do not disconnect equipment unless

power has been removed or the area is
known to be nonhazardous.

• Do not disconnect connections to this

equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this equipment
by using screws, sliding latches, threaded
connectors, or other means provided with
this product.

• Substitution of components may impair

suitability for Class I, Division 2.

• If this product contains batteries, they

must only be changed in an area known
to be nonhazardous.

AVERTISSEMENT:
Risque d’Explosion –
• Couper le courant ou s'assurer que

l'environnement est classé non dangereux
avant de débrancher l'équipement.

• Couper le courant ou s'assurer que

l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.

• La substitution de composants peut rendre

cet équipement inadapté à une utilisation
en environnement de Classe I, Division 2.

• S'assurer que l'environnement est classé non

dangereux avant de changer les piles.