Input Data
This is the I/O data the 1769-ADN sends to the DeviceNet master. All inputs are in words. For
more information, refer to the Compact I/O 1769-ADN DeviceNet Adapter User Manual,
publication
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
V16
V15
V14
V13
V12
V11
V10
V9
V8
V7
V6
V5
V4
V3
V2
V1
1
X
NS
V30
V29
V28
V27
V26
V25
V24
V23
V22
V21
V20
V19
V18
V17
2
Input data for slot 1*
3
“
“
“
n
Input data for slot 30*
* = The amount of input data for each module is based on the configuration of each I/O module done as part of the 1769-ADN configuration. Note that if an I/O
module is configured to have 0 words of input data, then there are no input data words for that module in the 1769-ADN’s input image.
V1 = Data invalid from slot 1 (1 = invalid data)
V2 = Data invalid from slot 2
V3 = Data invalid from slot 3
...
V30 =Data invalid from slot 30
where 1 = data invalid or a module error is detected; 0 = data valid, no module error
NS = Node address switch changed
where 1 = node address switch changed since power-up
X = Reserved