20 ControlLogix EtherNet/IP Module

Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

Status Indicators

Indicator

Status

Description

NET

Off

The module is not powered. Verify that there is
chassis power and that the module is completely
inserted into the chassis and backplane.
The module does not have a valid IP address. Make
sure the module has been configured with a valid IP
address.

Flashing green

The module has an IP address, but has no established
connections.

Green

The module has an IP address and at least one
established connection.

Red

The module is attempting to use an IP address
already in use on the network. Assign a unique IP
address to the module.

Link

Off

The module is not ready to communicate. Verify that
the module has power.

Green

The module is ready to communicate.

Flashing green

The module is communicating over the network.