Specifications, Specifications 22 – Rockwell Automation 1756-EN2T ControlLogix EtherNet/IP Module Installation Instructions User Manual
Page 22
 
22 ControlLogix EtherNet/IP Module
Rockwell Automation Publication 1756-IN603C-EN-P - April 2010
Specifications
Technical Specifications - 1756-EN2T
Attribute
1756-EN2T
Enclosure type rating
None (open-style)
Module location
Any slot in the ControlLogix chassis
Backplane current
1 A at 5.1V DC
Backplane current
3 mA at 24V DC
Isolation voltage
30V (continuous), Basic Insulation Type, Ethernet to 
backplane
No isolation between USB and backplane
Type tested at 510V AC for 60 s
Power dissipation, max.
5.1 W
Wire size
Ethernet connections:
RJ45 connector according to IEC 60603-7, 2 or 4 pair 
Category 5e minimum cable according to TIA 568-B.1 or 
Category 5 cable according to ISO/IEC 24702
Wiring category
2 - on Ethernet ports
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial 
Automation Wiring and Grounding Guidelines, publication
0-4.1
.
Temperature, surrounding 
air
60 °C (140 °F)
North American temp code
Series A: T5
Series B and C: T4A
Recommended USB cable 
for USB port
Samtec cable, PN RSP-119350
USB port
USB 1.1
USB device
USB series B receptacle