North American Hazardous Location Approval
The following information applies 
when operating this equipment in 
hazardous locations.
Informations sur l’utilisation de cet 
équipement en environnements 
dangereux.
Products marked “CL I, DIV 2, GP A, B, C, D” are 
suitable for use in Class I Division 2 Groups A, B, C, 
D, Hazardous Locations and nonhazardous 
locations only. Each product is supplied with 
markings on the rating nameplate indicating the 
hazardous location temperature code. When 
combining products within a system, the most 
adverse temperature code (lowest “T” number) 
may be used to help determine the overall 
temperature code of the system. Combinations of 
equipment in your system are subject to 
investigation by the local Authority Having 
Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements 
de Classe I Division 2 Groupes A, B, C, D dangereux et 
non dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d'identification qui indiquent 
le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés 
dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température 
global du système. Les combinaisons d'équipements 
dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de 
l'installation.
WARNING:
Explosion Hazard -
• Do not disconnect equipment
unless power has been removed 
or the area is known to be 
nonhazardous. 
• Do not disconnect connections to
this equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
Secure any external connections 
that mate to this equipment by 
using screws, sliding latches, 
threaded connectors, or other 
means provided with this product.
• Substitution of components may
impair suitability for Class I, 
Division 2.
• If this product contains batteries,
they must only be changed in an 
area known to be nonhazardous.
AVERTISSEMENT:
Risque d’Explosion – 
• Couper le courant ou s'assurer que
l'environnement est classé non 
dangereux avant de débrancher 
l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non 
dangereux avant de débrancher les 
connecteurs. Fixer tous les 
connecteurs externes reliés à cet 
équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou 
autres moyens fournis avec ce 
produit.
• La substitution de composants peut
rendre cet équipement inadapté à 
une utilisation en environnement de 
Classe I, Division 2.
• S'assurer que l'environnement est
classé non dangereux avant de 
changer les piles.