Rockwell Automation 1792-OB8PLP INSTL INSTR 8 OUTPUT MODULE User Manual

Page 11

Advertising
background image

ArmorBlock-LP 8 Output Module

11

Publication 1792-5.7 – December 1997

General Specifications

DeviceNet PowerVoltage

Current

11.0 – 25.0V dc
100mA

Dimensions

Inches
Millimeters

6.8H X 2.4W X 2.0D
172.1H X 60W X 51D

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Non-operating

Vibration

0 to 60

o

C (32 to 140

o

F)

–20 to 80

o

C (–4 to 176

o

F)

up to 100%
30 g peak acceleration, 11(+1)ms pulse width
50 g peak acceleration, 11(+1)ms pulse width
Tested 10 g @ 10–500Hz per IEC 68-2-6

Conductors

Refer to publication 1485-6.7.1 for information on
cabling for your DeviceNet module.

Enclosure

Meets or exceeds IP67

Agency Certification
(when product is marked)

CE marked for all applicable directives

This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory
and found to comply with ODVA Conformance Test Software
Version FT 1.3/1.1.

Advertising