Rockwell Automation 1792-OB8PLP INSTL INSTR 8 OUTPUT MODULE User Manual

Page 9

Advertising
background image

ArmorBlock-LP 8 Output Module

9

Publication 1792-5.7 – December 1997

30197–M

NS = Network Status Indicator

Output Short

Circuit Indicator

U

S

= Output Power

Supply Status Indicator

U

L

= Module Power Supply

Status Indicator

A = Output

Status Indicators

MS = Module Status

Indicator

Output

Connector

OUT

1

2

34

5

6

7

8

A

A

A

A

A

A

A

A

OUT

Network Status Indicator (NS)

Indication

Status

Flashing Green

On-line, not connected

Solid Green

Link OK, on-line connected

Flashing Red

At least 1 I/O connection is in the timed-out state

Solid Red

Incorrect baud rate, or a duplicate Mac ID exists

Module Status Indicator (MS)

Indication

Status

OFF

No power, or no network access

Flashing Green/OFF

On-line but not connected

Solid Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Solid Red

Critical failure

Output Short Circuit Indicator

Indication

Status

OFF

No shorted outputs

Solid Red

Shorted output

Output I/O Status Indicator (1A thru 8A)

Indication

Status

OFF

Output is off

Yellow

Output is on

Module and Output Power Supply Status Indicators U

S

and U

L

Indication

Status

OFF

Power supply is not functioning correctly

Green

Power Supply is operating