Refer to the table below for the word/bit definitions.
Bit
07
06
05
04
03
02
01
00
Consumes
O8A
O7A
O6A
O5A
O4A
O3A
O2A
O1A
Produces
Reser
ved
OF
Reserved
Where: O = Output
OF = Output fault status
Word
Bit
Description
Consumes
00–07 Output bits – when the bit is set (1), the output is on. Bit 00
corresponds to output 1A, bit 01 corresponds to output 2A, bit 02 to
output 3A, bit 03 output 4A, bit 04 corresponds to output 5A, bit 05
to output 6A, bit 06 to output 7A, and bit 07 to output 8A.
Produces
00–05 Reserved
Produces
06
OF = output fault status bit – indicates presence of field power and
overload condition.
07
Reserved
Troubleshoot with the Indicators
The ArmorBlock I/O module has the following indicators:
•
Network status indicators (NS)
•
Module status indicator (MS)
•
Individual Output status indicators A1 through A8
•
Power Status indicators
–
module power
–
output voltage
–