Connect the wiring to the armorblock module, Connecting the output wiring – Rockwell Automation 1792-OB8PLP INSTL INSTR 8 OUTPUT MODULE User Manual

Page 5

Advertising
background image

ArmorBlock-LP 8 Output Module

5

Publication 1792-5.7 – December 1997

Connect the Wiring to the ArmorBlock Module

This module uses quick disconnect, screw-on style connectors for:

I/O output wiring

the DeviceNet connector

the output power connector

30197–M

5-pin DeviceNet Mini-connector

Output Power

3-pin Mini-connector

Eight 5-pin Output Micro-connectors

1

2

34

5

6

7

8

A

A

A

A

A

A

A

A

OUT

OUT

Seven micro caps are included with your module. Use these caps to
cover and seal unused ports. Pinout diagrams for the connectors are
shown below.

!

ATTENTION: Make sure all connectors are securely
tightened to properly seal the connections against leaks and
maintain IP67 requirements.

Connecting the Output Wiring

Connect output wiring to the micro-connectors which screw into mating
connectors on the front of the block.

1

2

3

4

I/O Output Micro-Connector

Pin 1 = No connection

Pin 2 = Not used

Pin 3 = Negative/Return

Pin 4 = Signal A

(View into socket)