Connect the Wiring to the ArmorBlock Module
This module uses quick disconnect, screw-on style connectors for:
•
I/O output wiring
•
the DeviceNet connector
•
the output power connector
30197–M
5-pin DeviceNet Mini-connector
Output Power
3-pin Mini-connector
Eight 5-pin Output Micro-connectors
1
2
34
5
6
7
8
A
A
A
A
A
A
A
A
OUT
OUT
Seven micro caps are included with your module. Use these caps to
cover and seal unused ports. Pinout diagrams for the connectors are
shown below.
!
ATTENTION: Make sure all connectors are securely
tightened to properly seal the connections against leaks and
maintain IP67 requirements.
Connecting the Output Wiring
Connect output wiring to the micro-connectors which screw into mating
connectors on the front of the block.
1
2
3
4
I/O Output Micro-Connector
Pin 1 = No connection
Pin 2 = Not used
Pin 3 = Negative/Return
Pin 4 = Signal A
(View into socket)
5
Pin 5 = Ground