Chapter 3, 3 - configuring the module, Loop operation mode – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual
Page 27: Word 1, bits 0 and 1 for channel 1, Type of loop input, Word 1, bits 2-5 for channel 1, Loop operation mode -1, Word 1, bits 0 and 1 for channel 1 -1, Type of loop input -1, Word 1, bits 2-5 for channel 1 -1

1
Publication 1746-UM010B-EN-P - April 2001
Chapter
3
Configuring the Module
You configure the module by setting words and bits for each loop in
Configuration Block, N10:0–100, which your ladder logic uses to load
the module’s M1 file. We cover bit selections and word descriptions.
Refer to Table 3.B on page 3-13 for selections, units, and defaults.
Loop Operation Mode
Word 1, Bits 0 and 1 for Channel 1
Use these bits to select how you want the loop to perform:
Type of Loop Input
Word 1, Bits 2-5 for Channel 1
Use the following bits to select type J or K thermocouple; any other
bit setting is invalid:
Mode of Loop Operation
01
00
monitor the loop to indicate temperature and alarms
0
0
perform PID loop control with temperature indication and
alarms
0
1
disable the loop
1
0
invalid setting
1
1
TC
05
04
03
02
type J
0
0
0
0
type K
0
0
0
1