Chapter 5, 5 - control and autotune a loop, Controlling a loop – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual
Page 47: M1 configuration file, Output image table, Controlling a loop -1, M1 configuration file -1 output image table -1, Control and autotune a loop, Chapter

1
Publication 1746-UM010B-EN-P - April 2001
Chapter
5
Control and Autotune a Loop
This chapter explains how to:
•
control loop operation
•
autotune a loop
Controlling a Loop
At initial start–up, you must write the M1 configuration block to
establish the module’s mode of control. Then, you must update the
output image table any time you want to change the operating mode.
M1 Configuration File
You select the loop control mode in the configuration file:
Output Image Table
If you select “control–the–loop” mode, you control loop operation
with these words and bits in the output image table (abbreviated list):
Words
Bit 01 Bit 00 Lets you select
1, 26, 51, 76
for loops 1-4
0
0
monitor the loop
0
1
control the loop with PID
1
0
disable the loop
Words
Bit
Lets you
0-3
loops 1-4
00
enable or disable the loop
03
enable or disable autotune
4-7
n/a
enter run temperature setpoints
8-11
n/a
enter manual CV% output values
12
global for
all loops
01
invoke autotune
02
abort autotune
03
reset error codes