12 ArmorBlock MaXum 8 Input / 8 Output Module Series B

Publication 1792D-IN020B-EN-P - September 2000

Specifications

8 Input / 8 Output Module - Cat. No. 1792D-8BVT8D

Input Specifications

Max.

Min.

Inputs per block

8 - 3 wire or dry contact PNP or NPN devices or 4 -
4 wire PNP or NPN devices

Sensor Source Current (per
connector)

100mA total

-

Off-Wire Sense Current

0.5mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Output Specifications

Max.

Min.

Outputs per block 8 sourcing outputs labeled O0 through O7

Off Peak Blocking Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.5A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

4.0A

-

Surge Current - for 10ms,
repeatable every 2s

2.4A

-

No Load Sense Current (On-state)

0.18A

-

General Specifications

Indicators

Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red

Communication Rate

•125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
•250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
•500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)

DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.

25V dc max
150mA max (no sensors)

11V dc min
up to 1.4A (8 sensors
@ 50mA per sensor)