8 ArmorBlock MaXum 8 Input / 8 Output Module Series B

Publication 1792D-IN020B-EN-P - September 2000

Communicate With Your ArmorBlock MaXum I/O
Module

This ArmorBlock module’s I/O is exchanged with the master through a poll,
change-of-state, or cyclic connection.
The module consumes and produces I/O data as follows:

Cyclic - allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O message
to the module. The 8 input / 8 output module consumes the message,
updates outputs, and produces a response. The response has input data, input
faults, output faults, and the status of the Auxiliary power.
Change-of-State - productions occur when an input changes or a fault
condition occurs. If no input or fault condition change occurs within the
expected packet rate, a heartbeat production occurs. This heartbeat
production tells the scanner module that the I/O module is alive and ready to
communicate. Consumption occurs when data changes and the master
produces new output data to the I/O block.
Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Byte

4 Bytes

Polled

1 Byte

4 Bytes

Change-of-State

1 Byte

4 Bytes

Bit

07

06

05

04

03

02

01

00

Produces 0

I7

I6

I5

I4

I3

I2

I1

I0

Produces 1

OW-D

OW-C

OW-B

OW-A

ISC-D

ISC-C

ISC-B

ISC-A

Produces 2

OFLT7

OFLT6

OFLT5

OFLT4

OFLT3

OFLT2

OFLT1

OFLT0

Produces 3

RSVD

OPWR

RSVD

RSVD

RSVD

RSVD

RSVD

RSVD

Consumes 0

O7

O6

O5

O4

O3

O2

O1

O0

Where: OW= Off Wire RSVD= Reserved I = Input O = Output OPWR= Output Power
(Auxiliary Power) OFLT = Output fault ISC=Input Short Circuit in Sensor Source Voltage