6 ArmorBlock MaXum 8 Input / 8 Output Module Series B

Publication 1792D-IN020B-EN-P - September 2000

Use the micro caps to cover and seal unused ports. Pinout diagrams for the
connectors are shown next.

Please refer to publication 889-5.0 for Rockwell Automation cables and cord
sets offerings.

IMPORTANT

If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.

Input Micro-Connector

(View into Socket)

Pin 1 Sensor Source voltage
Pin 2 Input B

Pin 3 Return Logic Ground

1

Pin 4 Input A
Pin 5 Not Used

Output Micro-Connector

(View into Socket)

Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used

41452

1

Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.