Rockwell Automation 1738-IE2VM12 ArmorPoint 24V dc Analog Input Modules, Series A User Manual

Page 11

Advertising
background image

Publication 1738-IN003B-EN-E - June 2005

ArmorPoint 24V dc Analog Input Modules, Series A 11

Input Data Format

Signed integer

General Specifications
Calibration

Factory calibrated

Dimensions, Metric

120H x 72W x 42D

Dimensions, Imperial

4.72H x 2.83W x 1.65D

External dc Power Supply Voltage, Nom. 24V dc
External dc Power Supply Voltage Range 10…28.8V dc

External dc Power Supply Current

1738-IE2C - 10 mA @ 24V dc

1738-IE2V - 15 mA @ 24V dc

Indicators

1 green/red module status indicator, logic side
1 green/red network status indicator, logic side
2 green/red input status indicators, logic side

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60s

Keyswitch Position

3

Mounting Base Screw Torque

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Overvoltage Protection, Input

Fault protected to 28.8V dc

PointBus Current

75 mA @ 5V dc

Power Dissipation, Max.

1738-IE2C - 0.6 W @ 28.8V dc

1738-IE2V - 0.75 W @ 28.8V dc

Thermal Dissipation, Max.

1738-IE2C - 2.0 BTU/hr. @ 28.8V dc

1738-IE2V - 2.5 BTU/hr. @ 28.8V dc

Weight, Metric

0.29 kg

Weight, Imperial

0.64 lb

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 … 60 °C (-4 … 140 °F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 … 85 °C (-40 … 185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5…95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30 g

Non-operating 50 g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10-500 Hz

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30 MHz to 2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 Mhz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 Mhz

EFT/B Immunity

IEC 61000-4-4:

±3 kV at 5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:

±2 kV line-earth(CM) on shielded ports

Advertising
This manual is related to the following products: