I/O messages are sent to (consumed) and received from (produced)
the ArmorPoint I/O modules. These messages are mapped into the
processor’s memory. These ArmorPoint I/O analog input modules
produce 6 bytes of input data (scanner Rx) and fault status data. They
do not consume I/O data (scanner Tx).

Default Data Map for the ArmorPoint Analog Input Modules

1738-IE2CM12 and 1738-IE2VM12

Message size: 6 Bytes

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Produces
(Scanner Rx)

Input Channel 0 High Byte

Input Channel 0 Low Byte

Input Channel 1 High Byte

Input Channel 1 Low Byte

Status Byte for Channel 1

Status Byte for Channel 0

O
R

U
R

H
H
A

L

L
A

H
A

L
A

C
M

C

F

O

R

U
R

H
H
A

L

L
A

H
A

L
A

C
M

C

F

Consumes
(scanner Tx)

No consumed data

Where: CF = Channel Fault Status, 0 = no error, 1 = fault

CM = Calibration Mode; 0 = normal, 1 = calibration mode

LA = Low Alarm; 0 = no error, 1 = fault

HA = High Alarm; 0 = no error, 1 = fault

LLA = Low/Low Alarm; 0 = no error, 1 = fault

HHA = High/High Alarm; 0 = no error, 1 = fault

UR = Underrange; 0 = no error; 1 = fault

OR = Overrange; 0 = no error; 1 = fault