Publication 1746-RM001A-US-P

Output Functions 12-3

2.

2.

2.

2. The ladder logic program of the SLC processor must set the output file word 0,

bit 6 or bit 7 to inform the module that valid data is available. Bit 6 indicates
that data is available for port 1 and bit 7 indicates that data is available for port
2.

3.

3.

3.

3. The module automatically transfers the data to the destination serial port

(PRT1 or PRT2) from the SLC processor.

4.

4.

4.

4. The module sets the input file word 0, bit 6 or bit 7 to inform the SLC

processor that the transfer was successful.

5.

5.

5.

5. The ladder logic program of the SLC processor resets output file word 0, bit 6

or bit 7.

6.

6.

6.

6. The module resets the input file word 0, bit 6 or bit 7 on the same end of scan

cycle in which the output file word 0, bit 6 or bit 7 was reset.

Output File

Word 0, Bit 6

or Bit 7

PORT PRT1

PORT PRT2

SLC Processor

SLC Backplane

BASIC or BASIC-T Module

BYTE

COUNT

DATA BUFFER

PORT PRT1

PORT PRT2

SLC Processor

SLC Backplane

BASIC or BASIC-T Module

Input File

Word 0, Bit 6

or Bit 7

SLC Processor

SLC Backplane

BASIC or BASIC-T Module

Reset Output File

Word 0, Bit 6

or Bit 7

SLC Processor

SLC Backplane

BASIC or BASIC-T Module

Reset Input File

Word 0, Bit 6

or Bit 7

SLC Processor

SLC Backplane

BASIC or BASIC-T Module