Syntax – Rockwell Automation 1746-BAS BASIC LANGUAGE User Manual
Page 173

Publication 1746-RM001A-US-P
Output Functions 12-23
Syntax
PUSH [remote device node address]
PUSH [starting element offset (x2) of remote device file]
PUSH [number of words to be transferred]
PUSH [message time-out value]
CALL 93
POP [status of message instruction]
Table 12.7 Output Argument
Decimal
Output
Hexadecimal
Output
Description
0
00
Successful Completion.
2
02
Target node cannot accept the message at this time.
3
03
Target node cannot respond because message is too large.
4
04
Target node cannot respond because it does not understand
the command parameters.
5
05
module is off-line (not on link).
6
06
Target node cannot respond because requested function is
not available.
7
07
Target node does not respond.
10
0A
module detects illegal target node address.
11
0B
module detects illegal file number.
12
0C
module detects illegal target file element offset.
13
0D
module detects illegal target file length.
14
0E
module detects illegal time-out value.
16
10
Target node cannot respond because of incorrect command
parameters or unsupported command.
55
37
Message timed out (time-out value exceeded).
80
50
Target node is out of memory.
96
60
Target node cannot respond because file is protected.
231
E7
Target node cannot respond because length requested is too
large.
235
EB
Target node cannot respond because target node denies
access.
236
EC
Target node cannot respond because requested function is
currently unavailable.
241
F1
module detects illegal target file type.
250
FA
Target node cannot respond because another node is file
owner (has sole file access).
251
FB
Target node cannot respond because another node is
program owner (has sole access to all files).