Allen-Bradley Redundant Power Supplies
12
Publication 1771-IN030B-EN-P - July 2002
•
If you remove the terminal block and lay it on a flat
surface, insert the tool perpendicular to the wire (push
straight down ).
Insert wire here
Place tool here
This side plugs
into the connector
on module.
19966
C. After making the wiring connections, re-insert the terminal
block into the front plate on each processor.
Make sure the plug is completely inserted
and the locking prongs are engaged.
Once you have completed the tasks up to this point, you can turn the
power switches ON. Turn all the power switches on at the same
time. If everything is set up correctly, all P/S ACTIVE (green)
indicators will be on and all NON REDUNDANT SYSTEM
(yellow) indicators will be off.