Allen-Bradley Redundant Power Supplies

6

Publication 1771-IN030B-EN-P - July 2002

Set the I.D. Selection and Configuration Switches

Each power supply in a redundant system must be assigned a
different identification number. To do this, you must set the I.D.
selection switches located on the left side of the module
(shown below). A cutout in the metal cover of the module provides
access to these switches.

Switches

Are set

1, 2, 3, 4

for the power supply identification number

5, 6

based on the configuration zone

To set the switches:

1. Close the I.D selection switch (1, 2, 3, or 4) that represents the

number you selected for that power supply.

2. Determine the configuration zone being used so you can set

switches 5 and 6.

To determine the configuration zone, you must know the maximum
chassis current draw and the ambient air temperature of the chassis.

Maximum Current Draw (A)

Ambient Temperature

Configuration Zone

0Ć8

55°C

A

60°C

A

8Ć14

55°C

B

60°C

B

14Ć16

55°C

B

60°C

C

16Ć20

55°C

C

60°C

C

20Ć24

55°C

C

60°C

not permitted

3. Use the following table to position switches 5 and 6 based on the

configuration zone you determined.

If Configuration Zone Is

Set Switches

A

5 and 6 OPEN

B

5 CLOSED and 6 OPEN

C

5 OPEN and 6 CLOSED

I.D. Selection Switch

"