Rockwell Automation 1771-P4R_P6R Allen-Bradley Redundent Power Installation Instructions User Manual
Page 6

Allen-Bradley Redundant Power Supplies
6
Publication 1771-IN030B-EN-P - July 2002
Set the I.D. Selection and Configuration Switches
Each power supply in a redundant system must be assigned a
different identification number. To do this, you must set the I.D.
selection switches located on the left side of the module
(shown below). A cutout in the metal cover of the module provides
access to these switches.
Switches
Are set
1, 2, 3, 4
for the power supply identification number
5, 6
based on the configuration zone
To set the switches:
1. Close the I.D selection switch (1, 2, 3, or 4) that represents the
number you selected for that power supply.
2. Determine the configuration zone being used so you can set
switches 5 and 6.
To determine the configuration zone, you must know the maximum
chassis current draw and the ambient air temperature of the chassis.
Maximum Current Draw (A)
Ambient Temperature
Configuration Zone
0Ć8
55°C
A
60°C
A
8Ć14
55°C
B
60°C
B
14Ć16
55°C
B
60°C
C
16Ć20
55°C
C
60°C
C
20Ć24
55°C
C
60°C
not permitted
3. Use the following table to position switches 5 and 6 based on the
configuration zone you determined.
If Configuration Zone Is
Set Switches
A
5 and 6 OPEN
B
5 CLOSED and 6 OPEN
C
5 OPEN and 6 CLOSED
I.D. Selection Switch
"