Allen-Bradley Redundant Power Supplies

18

Publication 1771-IN030B-EN-P - July 2002

Problem 3

All P/S ACTIVE indicators show that the power supplies are OK,
but one or more NON REDUNDANT SYSTEM indicators are on,
indicating the desired redundancy is not available.

Check the redundant cables for continuity and

shorts. These shielded 6Ćconductor cables are 1:1.

P/S Active

ON?

yes

no

Done

Check switches 5 and 6 on all supplies to make

sure settings on each are the same.

P/S Active

Off?

yes

no

If ac voltage is OK, replace the

power supply, but do not turn

the ac power switch on.

Continue to test other supplies.

Try replacing the power supply with a known good

power supply.