Rockwell Automation 1771-P4R_P6R Allen-Bradley Redundent Power Installation Instructions User Manual

Page 5

Advertising
background image

Allen-Bradley Redundant Power Supplies

5

Publication 1771-IN030B-EN-P - July 2002

Set the Jumpers

Each power supply module has two jumpers located at the back of
the power supply near the edge connectors. The jumper selection
provides the proper voltage regulation for the different power supply
configurations. The power supply can be configured to support local
or remote sensing by setting the jumpers.

1. Locate the power supply jumpers on the back edge of the module

near the gold-plated edge connectors:

19965

2. Position the power supply module so that the jumpers and pins

are facing upward.

3. Use needle nose pliers to position the jumpers as shown in

this table.

For this configuration

Set jumpers to

All power supplies in a powerĆsupply

chassis (1771ĆPSC) connected to an

I/O chassis.

right position

All other configurations.

(These power supplies are shipped with

jumpers set to the left.)

left position

IMPORTANT

To avoid system malfunctions, set the jumpers
of power supplies in 1771 I/O chassis to the
left position.

Advertising