Specifications – Rockwell Automation 1792D2B0LP ArmorBlock LP2 2 Sinking Input Module User Manual

Page 9

Advertising
background image

ArmorBlock LP2 2 Sinking Input Module

9

Publication 1792D-5.43 - July 1999

Specifications

4 Input Module - Cat. No. 1792D-2BOLP

Sinking Input Specifications

Max

Min

Inputs per block

2- 3 wire or dry contact PNP devices

Sensor Source Current (per input)

100mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

General Specifications

Indicators

Network Status - red/green
Module Status - red/green
Point LED - yellow

Communication Rate

• 125Kbps @ 500 meters (1600 feet) for thick

cable, flat media length 375 meters (1230 feet)

• 250Kbps @ 200 meters (600 feet) for thick

cable, flat media length 150 meters (492 feet)

• 500Kbps @ 100 meters (330 feet) for thick

cable, flat media length 75 meters (246 feet)

DeviceNet Power:

Voltage
Current

25V dc max
125mA (no sensors)
300mA (full load)

11V dc min

Dimensions (assembled to base)
inches - (millimeters)

1.023H x 2.7W x 4.72D
(26)H x (68.5)W x (120)D

Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating

Non-operating

Vibration

-25 to 60

o

C (-13 to 140

°

F)

-25 to 80

o

C (-13 to 176

°

F)

Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11 (+1) ms pulse width
Tested 10g @ 10-500 Hz per IEC 68-2-6

Conductors

Publication DN-6.7.2

Enclosure

Meets or exceeds IP67

Agency Certification
(when product is marked)

• CE marked for all applicable directives

Product Data (user information)

Publication 1792-2.1

Advertising