Cable break procedures – Rockwell Automation 1790D-XXXX DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Series B User Manual

Page 15

Advertising
background image

DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 15

Publication

1790-IN014A-EN-P - March 2008

Cable Break Procedures

A cable break in any location between either of the following
produces data of 0 in the data table for all inputs down stream of the
cable break:

Base and digital input expansion module

Digital input expansion module and another digital input
expansion module

All digital-expansion inputs produce data of 0 if the expansion cable
is removed. No status is in the default produced assembly. Attribute
101 in the identity object reports module faults.

If no faults are present, an explicit message GET command returns 0.

If the ribbon cable is disconnected, it returns 0x04, which is for
module location change. The module status indicator also flashes
indicating a fault if an expansion is disconnected. Select an alternate
produced assembly that contains the expansion status byte, using the
EDS Properties configuration dialog.

I/O Status Indicators

Indicator

Status

Description

Each output

None

Output is not energized.

Green

Output is energized.

Each input

None

No valid input is present.

Green

Valid input is present.