Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output User Manual

Page 15

Advertising
background image

1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 15

Publication 1732E-IN006C-EN-E - June 2013

Power Connectors

Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as shown below.

Micro-style 4-Pin Input Male Receptacle

The power required by the module is based on a 4-pin micro-style connector system.
Power can be daisy chained through the module either left to right or right to left. The
standard configuration is with Module/Auxiliary power entering the module on the left
connector.

Both modules require two 24V DC (nominal) supplies. These supplies are called the
Module Power and the Auxiliary Power. The Module power supplies the microprocessor
and Ethernet portions of the module. The Auxiliary Power provides power for the analog
circuitry in both analog modules (1732E-IF4M12R and 1732E-OF4M12R) and for the
voltage or current outputs on the 173E-OF4M12R analog output module.

Internally, the Module Power and Auxiliary Power are electrically isolated.

IMPORTANT

The maximum current that any pin on the power connectors can

carry is 4 A.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this
equipment and all connected I/O must be powered from a source compliant
with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION: To comply with UL restrictions, this equipment must be powered
from a source compliant with the following: Limited Voltage/Limited Current.

ATTENTION: The device meets UL Type 1 Enclosure rating.

3

4

1

2

Male Input

Female Output

(View into receptacle)

Pin 1

Auxiliary power+

Pin 2

Module power+

Pin 3

Module power-

Pin 4

Auxiliary power-

45764

3

4

1

2

45763

Advertising