18 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules

Publication 1732E-IN006C-EN-E - June 2013

Indicator Status for Modules

Indicator

Status

Description

Module status

Off

No power applied to the device.

Flashing
red/green

The module is performing POST (Power-On Self Test), which
completes within 30 s.

Green

Device operating normally.

Flashing red

Module has experienced a recoverable fault.

Red

Unrecoverable fault – may require device replacement.

Network status

Off

The device is not initialized or the module does not have an
IP address.

Flashing green

The device has no CIP connections. The device has an IP
address, but no CIP connections are established.

Green

Device is online, has an IP address. CIP connections are
established.

Flashing red

One or more connections have timed out.

Red

The module has detected that its IP address is

already in use.

Flashing
red/green

The module is performing a power-on self test (POST).

Network link status

(Link 1/Link 2)

Off

No link established.

Green

Link established on indicated port at 100 Mbps.

Flashing green

Link activity present on indicated port at 100 Mbps.

Yellow

Link established on indicated port at 10 Mbps.

Flashing yellow

Link activity present on indicated port at 10 Mbps.

Auxiliary

Power status

Off

Auxiliary power off or not connected.

Green

Auxiliary power applied to device.