Certifications, Environmental specifications – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output User Manual

Page 22

Advertising
background image

22 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules

Publication 1732E-IN006C-EN-E - June 2013

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3 kV @ 5 kHz on power ports

±3 kV @ 5 kHz on signal ports

±3 kV @ 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5:

±2 kV line-line (DM) and ±2 kV line-earth (CM) on power ports

±500V line-line (DM) and ±1 kV line-earth (CM) on signal ports

±2 kV line-earth (CM) on communication ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

Meets IP65/66/67/69K (when marked)

Certifications

Certification (when
product is marked)

(1)

Value

c-UR-us

UL Recognized Component Industrial Control Equipment, certified for

US and Canada. See UL File E322657.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

Environmental Specifications

Attribute

Value